Metric
Conversion
Electrical Formulas
Conduit Weight
Maximum # of Conductors in Conduit
600 Volt Building Wire Weights & Ampacities
Ampacities of Insulated Conductors
Copper to Aluminum
Receptacle Configuration
|
Maximum
Number of THNN Conductors in
Trade Sizes of Conduit
Conduit
Trade Size (inches)
|
AWG
|
1/2
|
3/4
|
1
|
1
1/4
|
1
1/2
|
2
|
2
1/2
|
3
|
3
1/2
|
4
|
5
|
6
|
|
14
12
10
|
13
10
6
|
24
18
11
|
39
29
18
|
69
51
32
|
94
70
44
|
154
114
73
|
164
104
|
160
|
0
|
0
|
0
|
0
|
|
8
6
4
|
3
1
1
|
5
4
2
|
9
6
4
|
16
11
7
|
22
15
9
|
36
26
16
|
51
37
22
|
79
57
35
|
106
76
47
|
136
98
60
|
154
94
|
137
|
|
3
2
1
|
1
1
|
1
1
1
|
3
3
1
|
6
5
3
|
8
7
5
|
13
11
8
|
19
16
12
|
29
25
18
|
39
33
25
|
51
43
32
|
80
67
50
|
116
97
72
|
|
0
00
000
0000
|
0
|
1
1
1
1
|
1
1
1
1
|
3
2
1
1
|
4
3
3
2
|
7
6
5
4
|
10
8
7
6
|
15
13
11
9
|
21
17
14
12
|
27
22
18
15
|
42
35
29
24
|
61
51
42
35
|
|
250
300
350
|
0
|
0
|
1
1
1
|
1
1
1
|
1
1
1
|
3
3
2
|
4
4
3
|
7
6
5
|
10
8
7
|
12
11
9
|
20
17
15
|
28
24
21
|
|
400
500
|
0
|
0
|
0
|
1
1
|
1
1
|
1
1
|
3
2
|
5
4
|
6
5
|
8
7
|
13
11
|
19
16
|
Ampacity
Correction Factors for More than 3 Conductors in Raceway
|
No.
Conductors
Factor
|
4
to 6
.80
|
7
to 9
.70
|
10
to 20
.60
|
21
to 30
.45
|
31
to 40
.40
|
back
to top
|