Metric Conversion
Electrical Formulas
Conduit Weight
Maximum # of Conductors in Conduit
600 Volt Building Wire Weights & Ampacities
Ampacities of Insulated Conductors
Copper to Aluminum
Receptacle Configuration



Ampacities of Insulated Conductors
Rated 0-2000 Volts, 60º to 90ºC

Not more than three conductors in raceway or cable or earth (directly buried). Based on ambient temperature of 30ºC (86ºF)

Size
Temperature Rating of Conductor
Size

AWG
60ºC
(140ºF)
75ºC
(167ºF)
90ºC
(194ºF)
60ºC
(140ºF)
75ºC
(167ºF)
90ºC
(194ºF)

AWG
Types
Types
Types
Types
Types
Types
T
TW
UF
THW
THWN
XHHW
USE
RHH
THHN
XHHW
T
TW
UF
THW
THWN
XHHW
USE
RHH
THHN
XHHW
0
Copper
Aluminum
0
14
12
10
8
20
25
30
40
20
25
35
50
25
30
40
55
----
20
25
30
----
20
30
40
----
25
35
45
----
12
10
8
6
4
3
2
1
55
70
85
95
110
65
85
100
115
130
75
95
110
130
150
40
55
65
75
85
50
65
75
90
100
60
75
85
100
115
6
4
3
2
1
0
00
000
0000
125
145
165
195
150
175
200
230
170
195
225
260
100
115
130
150
120
135
155
180
135
150
175
205
0
00
000
0000
250
300
350
400
500
215
240
260
280
320
255
285
310
335
380
290
320
350
380
430
170
190
210
225
260
205
230
250
270
310
230
255
280
305
350
250
300
350
400
500
600
700
750
800
900
1000
355
385
400
410
435
455
420
460
475
490
520
545
475
520
535
555
585
615
285
310
320
330
355
375
340
375
385
395
425
445
385
420
435
450
480
500
600
700
750
800
900
1000


back to top